瓦斯發(fā)電機組遇到故障怎么解決才好?
一、如遇外電來(lái)電后瓦斯發(fā)電機不能自動(dòng)停機操作:
1、 If the gas generator can not automatically stop operation after external power supply:
1. 手動(dòng)停機,直接將轉換開(kāi)關(guān)由3點(diǎn)方向轉至12點(diǎn)方向,這是發(fā)電機停機;
1. Manual shutdown, directly turn the universal change-over switch from 3:00 to 12:00, which is the generator shutdown;
2. 打開(kāi)2#低壓配電柜,上方開(kāi)關(guān)為動(dòng)力開(kāi)關(guān),下方為照明開(kāi)關(guān),在照明開(kāi)關(guān)左邊有一小三角論,請操作人員員戴上絕緣手套,向上轉動(dòng)三角輪,待聽(tīng)到響聲后即已經(jīng)合閘送電;
2. Turn on the 2 ? low voltage distribution cabinet. The upper switch is the power switch, and the lower part is the lighting switch. There is a small triangle on the left side of the lighting switch. Please put on insulating gloves and turn the triangle wheel upward. After hearing the noise, the power supply has been switched on;
3. 關(guān)閉柜門(mén),將發(fā)電機由手動(dòng)狀態(tài)轉至自動(dòng)狀態(tài),恢復生產(chǎn)。
3. Close the cabinet door, turn the generator from manual state to automatic state and resume production.
二、如遇接到停電通知時(shí),請提前測試瓦斯發(fā)電機運行狀態(tài),確保停電時(shí)正常運行!啟機步驟如下:
2、 In case of power failure notice, please test the operation status of gas generator one day in advance to ensure normal operation during power failure. The starting steps are as follows:
1. 檢查瓦斯氣壓力、潤滑油油位、兩水箱的冷卻液液位,
1. Check gas pressure, lubricating oil level and coolant level of two water tanks,
2. 將發(fā)電機有自動(dòng)狀態(tài)轉換至手動(dòng)狀態(tài);將轉換開(kāi)關(guān)由3點(diǎn)方向左旋轉至12點(diǎn)方向為手動(dòng)狀態(tài);
2. Switch the generator from automatic state to manual state; rotate the universal transfer switch from 3-point direction to 12:00 direction to manual state;
3. 斷開(kāi)左下方發(fā)電機斷路器;將斷路器手柄扳至下方極為斷開(kāi);
3. Disconnect the generator circuit breaker at the lower left; pull the handle of the circuit breaker to the lower pole to disconnect it;
4. 啟動(dòng)發(fā)電機;將轉換開(kāi)關(guān)由12點(diǎn)方向向左旋轉至6點(diǎn)方向即為點(diǎn)火啟動(dòng)機器;
4. Start the generator; turn the universal change-over switch from 12:00 to 6:00 to start the machine;
5. 機器啟動(dòng)運行后請仔細關(guān)注電壓400V,頻率50HZ,轉速1500轉,運行10分鐘待水溫上升至60℃時(shí),將轉換開(kāi)關(guān)由6點(diǎn)方向旋轉至9點(diǎn)方向即為待機運行狀態(tài),5分鐘后機器會(huì )自動(dòng)停機;
5. After the machine is started, please pay attention to the voltage of 400V, frequency of 50Hz, speed of 1500 rpm, and run for 10 minutes. When the water temperature rises to 60 ℃, turn the universal change-over switch from 6 o'clock to 9:00 o'clock, which is the standby operation mode. After 5 minutes, the machine will stop automatically;
6. 測試結束后,請回復斷路器合閘狀態(tài),將轉換開(kāi)關(guān)由9點(diǎn)方向旋轉至3點(diǎn)方向,待停電時(shí)會(huì )自動(dòng)啟機。
6. After the test, please return to the closing state of the circuit breaker, turn the universal transfer switch from 9:00 to 3:00, and the machine will start automatically when the power is cut off.
上面的內容就是今天小編給大家介紹的內容了,我們真誠為您提供瓦斯發(fā)電機組服務(wù),您的滿(mǎn)意就是我們的責任,歡迎在網(wǎng)站下方留言:http://m.elmasticar.com
The above content is the content introduced to you today. We sincerely provide you with gas generator set service, and your satisfaction is our responsibility. Welcome to leave a message at the bottom of the website: http://m.elmasticar.com